KM1 Series
Multi-circuit Smart Power Monitor for back panel application
The KM1 platform enables the visualization of power consumption for back panel applications utilizing a master-slave concept. Up to four slave units can be connected to a master unit for simultaneous measurement of electric and non-electric parameters.
- Installation time consistently reduced.
- Mounting space reduced up to 24% compared to traditional monitoring products.
- Reduced number of devices: one platform can measure up to 36 circuits.
- Wiring reduced due to high speed innerbus communication and the power supply voltage from the master.
- Customizable platform for any applications
- Integrated Energy classification due to customizable internal thresholds
- High precision measurements even for currents below 5% of the nominal value.
- No VT required / Up to 7 pulse inputs accepted to collect also non electrical information
- Equipped with temperature input
- Free configuration tool KM//KE1 settings
- Dual system monitoring with one unit
Specifications & ordering info
Ordering information
Smart power monitors
Options (Order separately)
Separate or In-panel current transformer (CT)
Note: CT cables are not included with the CTs.
Current transformer (CT) cable
Note: Use the CT cable specified by OMRON or one manufactured by JST Mfg. Co.
You can also use a 1.25-B3A crimping terminal or AWG22 power cable.
Related devices (Sold separately)
Communications interface converter
Specifications
Ratings
Performance
Accuracy1 |
±1.0% FS, ±1 digit; or, ±2.0% FS, ±1 digit for voltage across Vtr under the same conditions |
||||
However, the accuracy is ±2.0% FS, ±1 digit for the phase-S current for a three-phase, three wire circuit and the phase-N current for a single-phase, three wire circuit under the same conditions. |
|||||
However, the accuracy is ±2.0% FS, ±1 digit for the phase-S current for a three-phase, three wire circuit and the phase-N current for a single-phase, three wire circuit under the same conditions. |
|||||
Power factor2 |
±5.0% FS at an ambient temperature of 23° C, rated input, rated frequency, and a power factor of 0.5 to 1 to 0.5 |
±5.0% FS at an ambient temperature of 23° C, rated input, rated frequency, and a power factor of 0.5 to 1 to 0.5 |
|||
±5°C two hours after the power supply is turned ON (after performing any adjustments for the ambient temperature) |
|||||
CompoWay/F: 0 to 99, Modbus:1 to 99 When a switch operation is performed to set the protocol to Modbus when the node number is set to 0, the node number is automatically changed to 1. |
|||||
Data length3 |
|||||
Stop bits3 |
CompoWay/F: 1 bits or 2 bits; Modbus: 1 bit with priority, 2 bits without priority |
||||
Special CTs
Current Transformer (CT) Cable
KM-series Power monitor models
(maximum width of 45 × 5 when five Units are linked together) |
||||
KE1-DRT-FLK DeviceNet communications unit
Can be a combination of multidrops and T-branching (for both main and branch lines). |
||||
5 dedicated lines (2 signal lines, 2 power lines, and 1 shield) |
||||
Maximum network length4 |
||||
1. Based on JISC1111, without special CT error, at ambient temperature of 23° C, rated input, and rated frequency. Applicable to 2nd, 3rd, 5th, 7th, 9th, 11th, and 13th harmonics.
1. Based on JISC1111, without special CT error, at ambient temperature of 23° C, rated input, and rated frequency. Applicable to 2nd, 3rd, 5th, 7th, 9th, 11th, and 13th harmonics.
How can we help you?
If you have a question or would like to ask for a quote, please contact us or send a request.
Ota minuun yhteyttä KM1 Series

Kiitos yhteydenotostasi. Otamme teihin yhteyttä mahdollisimman pian.
Meillä on teknisiä ongelmia. Emme ole pystyneet vastaanottamaan lomakettasi. Pahoittelemme ja pyydämme yrittämään uudelleen myöhemmin.
DownloadTarjous KM1 Series
Tällä lomakkeella voit pyytää tarjouksen valitsemastasi tuotteesta. Täytäthän kaikki *-merkityt kentät. Henkilökohtaisia tietojasi käsitellään luottamuksellisesti.

Kiitos tarjouspyynnöstä. Toimitamme tarvittavat tiedot teille mahdollisimman pian.
Meillä on teknisiä ongelmia. Emme ole pystyneet vastaanottamaan lomakettasi. Pahoittelemme ja pyydämme yrittämään uudelleen myöhemmin.
DownloadDownloads